Business Building

Introduction

Business Building is designed and constructed to support business operations. This category includes any building or section used for business transactions, record-keeping, and related activities, such as professional offices and service facilities. It also covers public institutions like city halls, town halls, courthouses, and libraries, as long as their primary function is conducting public business and maintaining records.

These Buildings and structures are under Group E shall be further subdivided as follows:

Subdivision E-1

Building for Offices, Banks, Professional Establishments

Subdivision E-2

Buildings for Laboratories, Outpatient Clinics, Research Establishments

Subdivision E-3

Buildings for Electronic Data Processing Centres, Computer Installations

Subdivision E-4

Buildings for Telephone Exchanges

Subdivision E-5

Building for Broadcasting Stations, TV Stations and Air Traffic Control Towers

According to the Telangana Disaster Response and Fire Services Department’s circular memorandum,

• A Fire NOC is required for buildings that exceed 15 meters in height but the setback of these buildings must be as per GO 168 MA&UD

According to the National Building Code of India (NBC),

• A Fire Safety Audit and certifications are mandatory, which shall be obtain by the competent person or charted fire auditor by the council

Sno: Type of Building Occupancy Fire Extinguisher Fire Hose Reel Fire Hydrant Fire Sprinkler Fire Alarm System (Manually)
Fire Alarm System (Automatic)
BUSINESS BUILDINGS (E)
E-1 E-5
Buildings of E-1 to E-5
a)
Less than 10m in height
RRR R
(*Note 4)
R NR
b) Above 10m but not exceeding 15m in height RRR R
(*Note 4)
R R
c) AAbove 15m and up to 24m in height R R R R R R
d) AAbove 24m and up to 30m in height R R R R R R
e)
Above 30m in height
R R R R R R

R- Required NR- Not Required

These are preliminary details drawn from the National Building Code of India. For more precise information, please refer to Table 7 of NBC 2016.

Notes

MOEFA System shall also include talk-back system and public address system for the occupancies given in the table for (d) (I) (iii) under A-5, (a) (I) (iv) and (a) (2) under C-I, and (a) (2) under D-I to D-5, in all buildings 15 m and above in height, except for A-3 and A-4 occupancies where these shall be provided for buildings of height 24 m and above. These shall also be provided in car parking areas more than 300 m2 and in multi-level car parking irrespective of their areas.

Automatic detection and alarm system is not required to be provided in car parking area. Such detection system shall however be required in other areas of car parking such as electrical rooms, cabins and other areas.
Buildings above 15 m in height are not to be permitted for occupancies A-I and A-2.
Required to be installed in basement, if area of basement exceeds 200 m2.
Required to be provided if basement area exceeds 200 m2.
Additional value given in parenthesis shall be added if basement area exceeds 200 m2.

Required to be provided for building with more than two storeys (Ground + One).

Required to be provided for building with height above 15m and above.
Sprinklers shall be fed water from both underground static water storage tank and terrace tank.